Portable generator
GE SX-6500 YDT Super silenced · Diesel
Super silenced portable diesel generator with YANMAR L 100 V, 6.5 kVA / 5.2 kW, 3-phase, 400/230 V.
- LTP
- 6.5 kVA
- PRP
- 5.7 kVA
- Voltage
- 3-phase
- Fuel
- Diesel
Classification
Applications of the portable generator
This model is suitable for temporary power supply on construction sites, during service work, at events and for mobile applications. Power, fuel and voltage are summarized for technical selection.
Technical data
Technical data at a glance

Features
- Bunded base suitable to contain any liquids leakage from engine avoiding environmental pollution
- The rounded edges of the canopy designed for rainwater drainage away
- Engine cowling side, can be completely opened, which facilitates all maintenance operations
- Central lifting eye
- Circuit breaker and ELCB-GFI (Ground Fault Interruptor)
- Emergency stop button
- Supersilenced
- Ready for connection to automatic transfer unit EAS
- Automatic voltage regulator
- Meets EC directives for noise and safety
Engine and generator data
General data
* Acoustic power in accordance with Directive 2000/14/EC
Control panel
- Start and stop engine key
- Engine protector thermal circuit breaker: 1x5A
- Low oil pressure warning light with shutdown
- Low fuel warning light with shutdown
- Battery charge warning light fault
- Local-Remote Start switch. Switch on Remote position for operating with Auto Transfer Switch EAS
- EAS plug
- Digital multifunction meter : A.C. Voltmeter - Frequencymeter - Total Hoursmeter - Partial Hoursmeter (resettable) - Battery voltmeter
- Emergency stop button
- Earth leakage with integral over-current circuit breaker
- Circuit breaker for 400V socket
- Output sockets 1x 400V 16A 3P+N+T CEE IP671x 230V 16A 2P+T CEE IP671x 230V 16A 2P+T Schuko
Definitions:
Ambient conditions for power ratings: Temperature 25°C, altitude 1000 m above sea level, relative humidity 30%.
Standby power (LTP): Emergency power. Maximum available power for operation with variable loads, limited to 500 hours per year. Overload is not permitted.
Prime Power (PRP): Prime power with variable loads. Maximum available power for operation with variable loads for an unlimited number of hours per year. The average power during a 24-hour period must not exceed 70% of the stated value.
Continuous power (COP): Continuous power with constant load. Maximum available power for operation with constant load for an unlimited number of hours per year.
Note: The data is taken from the original technical datasheet. Displayed values are nominal values, may change without prior notice and may vary by up to ±5%.
Inquiry
Prepare inquiry
The selected model is already included. Add your requirements regarding price, delivery time or technical specifications.
- Model and core data are added automatically.
- Price, availability and delivery time can be requested directly.
- Technical requirements can be added in the message field.
Download & comparison
Open datasheet or compare further portable generators
Verified technical answer
GE SX-6500 YDT at a glance
GE SX-6500 YDT is a three-phase diesel portable generator with 5.7 kVA / 4.6 kW PRP and 6.5 kVA / 5.2 kW LTP. The values below are taken from the assigned, field-audited manufacturer datasheet.
| PRP output | 5.7 kVA / 4.6 kW |
|---|---|
| LTP output | 6.5 kVA / 5.2 kW |
| Phase / voltage | 3-phase / 400/230 V |
| Fuel | Diesel |
| Engine | YANMAR L 100 V |
| Tank / runtime | 23 lt. / 19 h |
How should the output be interpreted?
PRP and LTP describe different rated operating conditions. The connected loads, starting currents and operating duration still need to be checked.
What confirms these values?
The visible values and structured data use the same field-audited manufacturer datasheet.