Portable generator

Portable generator

GE 15 YSXC Super silenced · Diesel

Super silenced portable diesel generator with YANMAR 3TNV88, 15 kVA / 12 kW, 3-phase, 400/230 V.

LTP
15 kVA
PRP
14 kVA
Voltage
3-phase
Fuel
Diesel
GE 15 YSXC15 kVA / 12 kW (LTP) • 3-phase • Diesel
YANMAR diesel engine
max. 15 kVA
3-phase
CE-compliant
Electric start

Classification

Applications of the portable generator

This model is suitable for temporary power supply on construction sites, during service work, at events and for mobile applications. Power, fuel and voltage are summarized for technical selection.

Power & voltage14 kVA (PRP) / 15 kVA (LTP) for 400/230 V 3-phase output.
Engine & fuelYANMAR 3TNV88 with diesel operation, water-cooled.
Tank & handlingTank 60 lt.; runtime at 75% PRP 23 h; dry weight 565 kg; protection degree IP 23; dimensions 1720 x 1000 x 1127 mm.

Technical data

Technical data at a glance

GE 15 YSXC

Features

  • Combined system voltage regulation: electronic AVR + Compound
  • External fuel supply with anti-shock protection
  • Engine cowling side, can be completely opened, which facilitates all maintenance operations
  • The recessed control panel is lockable and houses the sockets and machine controls
  • Central lifting eye
  • Ready for connection to automatic transfer unit EAS (AMF + ATS)
  • Meets EC directives for noise and safety
Power kVA 14 kVA (PRP)15 kVA (LTP)
Power kW 11.2 kW (PRP)12 kW (LTP)
Voltage (3-phase) 400/230 V
Cooling system Water-cooled
Fuel Diesel

Engine and generator data

EngineYANMAR 3TNV88
CoolingWater-cooled
Cylinders3
Displacement1.6 lit
Speed governorMechanical
Oil sump capacity2.8 lit. (min) - 6.7 lit. (max)
Fuel consumption 110%3.8 lit./h
Fuel consumption 100% PRP3.4 lit./h
Fuel consumption 75% PRP2.6 lit./h
Fuel consumption 50% PRP1.9 lit./h
Generator data
Main featuresSYNCHRONOUSOUS, THREE-PHASE, SELF-EXCITED, SELF-REGULATED, BRUSHLESS
AVR modelHVR-10 KE
Voltage regulation precision± 1.0 %

General data

Voltage400/230 V
Phase3-phase
Protection degreeIP 23
Tank capacity60 lt.
Runtime at 75% PRP23 h
Starter battery12 Vdc -62Ah
Dimensions (L x W x H)1720 x 1000 x 1127 mm
Dry weight of machine565 kg
Measured sound power level Lwa (pressure LpA) *91 dB(A) (66 dB(A) @ 7 m)
Guaranteed sound power level Lwa (pressure LpA) *92 dB(A) (67 dB(A) @ 7 m)

* Betrieb in Räumen unter Berücksichtigung der Richtlinie 2000/14/EC

Control panel

  • Controller EP6
  • Fuel level gauge
  • Siren
  • Emergency stop button
  • Local-Remote Start switch
  • EAS plug
  • TCM 35 remote control plug
  • Voltmeter switch 0 - RS - ST - TR
  • Four pole circuit breaker
  • ELCB-GFI (Ground Fault Interruptor) 30 mA
  • Output sockets 1x 400V 32A 3P+N+T CEE1x 400V 16A 3P+N+T CEE1x 230V 16A 2P+T CEE1x 230V 16A 2P+T SCHUKO
  • Circuit breakers for 230V 16A sockets

Definitions:

Ambient conditions for power ratings: Temperature 25°C, altitude 1000 m above sea level, relative humidity 30%.

Standby power (LTP): Emergency power. Maximum available power for operation with variable loads, limited to 500 hours per year. Overload is not permitted.

Prime Power (PRP): Prime power with variable loads. Maximum available power for operation with variable loads for an unlimited number of hours per year. The average power during a 24-hour period must not exceed 70% of the stated value.

Continuous power (COP): Continuous power with constant load. Maximum available power for operation with constant load for an unlimited number of hours per year.

Note: The data is taken from the original technical datasheet. Displayed values are nominal values, may change without prior notice and may vary by up to ±5%.

Inquiry

Prepare inquiry

The selected model is already included. Add your requirements regarding price, delivery time or technical specifications.

  • Model and core data are added automatically.
  • Price, availability and delivery time can be requested directly.
  • Technical requirements can be added in the message field.
Inquiry for:Portable generatorModel and key data are included

Download & comparison

Open datasheet or compare further portable generators

Verified technical answer

GE 15 YSXC at a glance

GE 15 YSXC is a three-phase diesel portable generator with 14 kVA / 11.2 kW PRP and 15 kVA / 12 kW LTP. The values below are taken from the assigned, field-audited manufacturer datasheet.

PRP output14 kVA / 11.2 kW
LTP output15 kVA / 12 kW
Phase / voltage3-phase / 400/230 V
FuelDiesel
EngineYANMAR 3TNV88
Tank / runtime60 lt. / 23 h

How should the output be interpreted?

PRP and LTP describe different rated operating conditions. The connected loads, starting currents and operating duration still need to be checked.

What confirms these values?

The visible values and structured data use the same field-audited manufacturer datasheet.

Technical data reviewed on 20 August 2026 by GGG German Generator GmbH – Technical Project Consulting.Open verified datasheet