Portable generator
GE SX-9000 KDM Super silenced · Diesel
Super silenced portable diesel generator with REHLKO KDW702, 9.2 kVA / 7.2 kW, 1-phase, 230 V.
- LTP
- 9.2 kVA
- PRP
- 8.3 kVA
- Voltage
- 1-phase
- Fuel
- Diesel
Classification
Applications of the portable generator
This model is suitable for temporary power supply on construction sites, during service work, at events and for mobile applications. Power, fuel and voltage are summarized for technical selection.
Technical data
Technical data at a glance

Features
- Control panel with digital control unit
- Automatic voltage regulation “AVR”
- Circuit breaker
- ELCB-GFI (Ground Fault Interruptor) 30mA
- Bunded base suitable to contain any liquids leakage from engine avoiding environmental pollution
- Central lifting eye
- The rounded edges of the canopy designed for rainwater drainage away
- Canopy with large opening to allow easy maintenance (replacement of air, oil, fuel filters)
- Large fuel tank
- Fuel level sensor
- External plugs for oil and water drainage
- Emergency stop button
Engine and generator data
General data
* Acoustic power in accordance with Directive 2000/14/EC
Control panel
- Controller InteliNano Plus
- Supply switch
- Engine protection circuit breakers :1x30A - 1 x 16A
- Emergency stop button
- Siren
- TCM 35 remote control plug
- PAC (ATS) plug 16 poles (automatic control panel only)
- Battery charger (automatic control panel only)
- Fuses: 1x 2A
- Circuit breaker
- Earth leakage circuit breaker (GFI)
- Output sockets 1x 230V 32A 2P+T CEE IP 67
Definitions:
Ambient conditions for power ratings: Temperature 25°C, altitude 1000 m above sea level, relative humidity 30%.
Standby power (LTP): Emergency power. Maximum available power for operation with variable loads, limited to 500 hours per year. Overload is not permitted.
Prime Power (PRP): Prime power with variable loads. Maximum available power for operation with variable loads for an unlimited number of hours per year. The average power during a 24-hour period must not exceed 70% of the stated value.
Continuous power (COP): Continuous power with constant load. Maximum available power for operation with constant load for an unlimited number of hours per year.
Note: The data is taken from the original technical datasheet. Displayed values are nominal values, may change without prior notice and may vary by up to ±5%.
Inquiry
Prepare inquiry
The selected model is already included. Add your requirements regarding price, delivery time or technical specifications.
- Model and core data are added automatically.
- Price, availability and delivery time can be requested directly.
- Technical requirements can be added in the message field.
Download & comparison
Open datasheet or compare further portable generators
Verified technical answer
GE SX-9000 KDM at a glance
GE SX-9000 KDM is a single-phase diesel portable generator with 8.3 kVA / 7.5 kW PRP and 9.2 kVA / 8.3 kW LTP. The values below are taken from the assigned, field-audited manufacturer datasheet.
| PRP output | 8.3 kVA / 7.5 kW |
|---|---|
| LTP output | 9.2 kVA / 8.3 kW |
| Phase / voltage | 1-phase / 230 V |
| Fuel | Diesel |
| Engine | KOHLER KDW702 |
| Tank / runtime | 38 lt. / 14.5 h |
How should the output be interpreted?
PRP and LTP describe different rated operating conditions. The connected loads, starting currents and operating duration still need to be checked.
What confirms these values?